SHI Hai-jun. Method for Series Coupling Condensers Insulation Test without Disconnection[J]. High voltageapparatus, 2008, (3): 277-279.DOI:
Method for Series Coupling Condensers Insulation Test without Disconnection
摘要
针对耦合电容器特点
提出不拆头试验方法
即采用下节正接法与上下两节并联反接法相结合
分别检测上下节耦合电容器的电容值与介质损耗等。现场试验表明
通过不拆头试验
可以方便、准确检测上下节耦合电容器绝缘
极大地减少了检修工作量
保障了设备和人员的安全。通过不停电检测方法对耦合电容器进行测量
可以实时分析其绝缘运行状况
及时发现绝缘缺陷
适于推广应用。
Abstract
According to the features of series coupling condensers
the values of copacitance and dielectric loss of upper and lower sections of the series coupling concensers were detected respectively via connecting the lower section consequently and connecting both lower and upper sections reversely without disconnection. Field test shows that this method can detect the upper and lower coupling condensers insulation conveniently and accurately with reduced workload
and moreover can make equipment and person more safe. On-line measurement of coupling condensers makes it possible to analyze real-time insulation status