针对甘肃某供电局氧化锌避雷器(MOA)应用现状
对电站型和线路型MOA结构进行分析
发现110 kV某变电站1号主变压器35 kV侧B相避雷器泄漏电流异常
通过带电检测、停电试验、解体检查
最终确认为受潮故障。
Abstract
This paper aimed at the MOAs in a power supply bureau of Gansu Province to analyze the structures of line MOA and power station MOA.An example to deal with abnormal on line current detection of 35 kV B-phase MOA in a 110 kV transformer substation was introduced.By analyzing the results of on line measurement