WEI Jun-mei1, LIN Xin1, WEI Chang-yu3. Analysis and Research on Electromagnetism Induction of Busbar Tube for 550 kV SF6 GIS[J]. High voltageapparatus, 2007, (6): 416-418+422.
WEI Jun-mei1, LIN Xin1, WEI Chang-yu3. Analysis and Research on Electromagnetism Induction of Busbar Tube for 550 kV SF6 GIS[J]. High voltageapparatus, 2007, (6): 416-418+422.DOI:
Analysis and Research on Electromagnetism Induction of Busbar Tube for 550 kV SF6 GIS
Induced current and power loss and impedance of busbar used in 550kV/4000A SF6 GIS under normal situation were calculated for different tube material thickness in multiple-point-earthing system and single-point-earthing system.The effects of earthing system and tube material and thickness to the loss power and impendence were compared in detail.In multiple-point-earthing system
if the tube material was aluminum or stainless steel
the power loss would decreasing as tube thickness increasing;but if the tube material was boiler steel
the power loss almost didn’t change when the increasing of tube thickness;the power loss of stainless steel and boiler steel would be 14 times and 32 times of that of aluminum respectively.In single-point-earthed system
the power loss increases with the increase of wall thick of tube.If the material of tube is aluminum or stainless steel
the power loss of tube in single-point-earthing system was much less than that in multiple-point-earthing system;if the material was boiler steel
the power loss in single-point-earthing system was 2 times of that in multiple-point-earthing system.These were determined by distribution character of induced current in the tube.
Calculation and Measurement Analysis for Induced Voltage and Current of 500 kV/220 kV Mixed-voltage and Four-circuit Transmission Lines on the Same Tower
Induced Current Switching Tests of the Earthing Switches in Type ZFW-500 CIS
Questions of HV Earthing Switch Switching Induced Current
Application of Class B Earthing Switch Switching Induced Current in Gezhouba Hydropower Station
Research on Switching Induced Voltage and Current by Earthing Switch in 500/220 kV Four-circuit on One Tower
Related Author
LI Yamei
HUANG Shiyang
NING Linru
CHEN Xiao
WANG Chenxing
LIN Tao
PENG Zhaowei
XU Dangguo
Related Institution
State Grid Jibei Electric Power Co., Ltd. Electric Power Science Research Institute
State Grid Jibei Electric Power Co., Ltd.
Beijing Power Transmission and Transformation Co., Ltd.