理论分析表明
由于操作过电压主要产生在中压电动机的相间
而现行的ZnO避雷器皆为星型接线
所以
它对中压电动机相对地的绝缘可起到一定的保护作用
而对相间绝缘则完全不能进行保护
为此
文中阐述了TBP抑制中压电动机操作过电压的特性及其应用
Theoretical analysis shows that the switching overvoltage mainly exists between phase to phase of medium voltage motor
whilst the present protection is connected in Y mode
therefore
the phase to neutral insulation can be protected
but the phase to phase insulation can not be protected.For this reason
this paper presents the application of TBP to the suppression of overvoltage.