Analysis of the Internal Electric Field in Vacuum Interrupter with the Shield Fiyed by Ceramic Supporters[J]. High voltageapparatus, 1992, (3): 11-14.DOI:
Analysis of the Internal Electric Field in Vacuum Interrupter with the Shield Fiyed by Ceramic Supporters
摘要
计算和分析了瓷柱式真空灭弧室的内部电场
同时经冲击耐压试验证明:瓷柱被金属蒸气污染是造成此种结构灭弧室容易发生内击穿的原因。
Abstract
The internal electric field in vacuum interrupter with the shield supported by ceramic supporters is calculated and analysed. The results show that the cause of the breakdown in this type of interrupter is the contamination of metal vapor on the surface of ceramic supporters.
Static Potential Measurement on the Shield of Vacuum Interrupters
Statistical Estimation of Static Breakdown Voltage of Vacuum Interrupters
Research on Electric Filed Analytical Model Near EHV Transmission Lines Under Thunderclouds
Research on Electric Field Distribution Characteristics Simulation Under Typical Defects in the Scaled Model of Valve Side Bushing of UHV Converter Transformer
Study on Axial Magnetic Field Measurement and Magnetic Field Saturation Characteristics of Iron Type Bipolar AMF Contact
Related Author
王承玉
王季梅
陈轩恕
何俊佳
邹积岩
程礼椿
WANG Weifang
ZHANG Yilong
Related Institution
西安交通大学
西安交通大学 710049
Key Laboratory of Control of Power Transmission and Conversion, Shanghai Jiao Tong University
State Grid Shanghai Municipal Electric Power Company
NARI Group Corporation/State Grid Electric Power Research Institute