Shang Zhenqiu. The Analysis on Whether ZnO Surge Arrester Can Protect H.V. Motor from Damage Caused by Switching Overvoltage of Vacuum Circuit Breaker[J]. High voltageapparatus, 1989, (3): 3-6.
Shang Zhenqiu. The Analysis on Whether ZnO Surge Arrester Can Protect H.V. Motor from Damage Caused by Switching Overvoltage of Vacuum Circuit Breaker[J]. High voltageapparatus, 1989, (3): 3-6.DOI:
The Analysis on Whether ZnO Surge Arrester Can Protect H.V. Motor from Damage Caused by Switching Overvoltage of Vacuum Circuit Breaker
摘要
通过理论分析表明
由于操作过电压主要产生在高压电动机的相与相之间
而现行的ZnO避雷器皆为星形接线
所以
它对高压电动机相对地的绝缘可起到一定的保护作用
而对相对相之间的绝缘则完全不能进行保护。
Abstract
Theoritical analysis shows that switching overvoltage mainly arises between phase and phase
so Y-scheme of ZnO surge arrester can only protect the phase-earth insulation of H.V. motor in some way but not phase -phase insulation.