对采用屏蔽电阻的直流电阻分压器进行了分析
推导出其误差的计算式
利用此式合理地选择分压器各部分的结构尺寸
设计、制造了一台250kV时准确度达0.1级、150kV时准确度达0.02级的高精密度直流电阻分压器
In this paper
the DC resistor voltage dividers with shield resistor have been analysed
a calculating formula of errors has been obtained. Using this formula
the structure and size of dividers can be chosen. Two high accurate dividevs ( 250kA
accuracy 0.1 and 150kV accuracy 0.02 respectively ) were designed and made.