LIU Gang1, LIAO Rui-jin2, FENG Yun1, et al. Temperature Influence on Parameters of Return Voltage Measurement of Oil-paper Insulation System in Transformer[J]. High voltageapparatus, 2010, 46(1): 80-84.
LIU Gang1, LIAO Rui-jin2, FENG Yun1, et al. Temperature Influence on Parameters of Return Voltage Measurement of Oil-paper Insulation System in Transformer[J]. High voltageapparatus, 2010, 46(1): 80-84. DOI: 10.13296/j.1001-1609.hva.2010.01.009.
Temperature Influence on Parameters of Return Voltage Measurement of Oil-paper Insulation System in Transformer
Return voltage measurement(RVM) can be conveniently used to diagnose the insulating condition of transformers in field.The temperature of insulation system imposes significant effect on the results of RVM.In order to understand the changing regularities of RVM parameters
the test results of the RVM parameters are exactly compared and analyzed at different temperatures of insulation system in this paper.RVMs were conducted for the insulating system composed of 25# transformer oil and kraft paper at different temperatures
and the changing regularities of RVM parameters were obtained.The results show that the maximum of RVM and its initial slope increase exponentially with the elevating temperature of the insulation system
the central time constant decreases exponentially with the elevating temperature of the insulation system
and the measurement error is smaller when the temperature of the insulation system is lower.