WANG Wei, XIA Zhong-yuan, HAN Jin-hua, et al. Field AC Voltage Withstand Test of UHV Shunt Reactors[J]. High voltageapparatus, 2010, 46(1): 61-63+67. DOI: 10.13296/j.1001-1609.hva.2010.01.019.
Field AC Voltage Withstand Test of UHV Shunt Reactors
AC voltage withstand test is the most direct and effective method to judge the Insulation Performance of Electrical Equipments.In this paper
an AC voltage withstand test of ultra high voltage(UHV for short) shunt reactors at 1 000 kV AC Nanyang switch-gear station was conducted.The test frequency could be limited within 45 ~65 Hz by adopting serial resonance method and properly combining compensating capacitors and reactors.This test needs less test devices and lower power supply capacity
thus to be suitable for field AC voltage withstand test of UHV Shunt Reactors.