HUANG Hai-bo1, ZHANG Jin1, KOU Xiao-shi2, et al. Simulation Study on Overvoltage Response Characteristic of Bushing Divider Subsystem[J]. High voltageapparatus, 2010, 46(1): 44-48.
HUANG Hai-bo1, ZHANG Jin1, KOU Xiao-shi2, et al. Simulation Study on Overvoltage Response Characteristic of Bushing Divider Subsystem[J]. High voltageapparatus, 2010, 46(1): 44-48. DOI: 10.13296/j.1001-1609.hva.2010.01.022.
Simulation Study on Overvoltage Response Characteristic of Bushing Divider Subsystem
This paper studies an overvoltage on-line monitoring system based on transformer bushing tap.A model of its core capacitive bushing divider subsystem is established and simulated by the electromagnetic transient program ATP.Simulation of square wave response characteristic is conducted with the model
and the comparison between simulation result and laboratory measurement verifies the validity of the simulation.This simulation method may facilitate the design of the other types of bushings.Furthermore
the outputs of the overvoltage on-line monitoring system are obtained via the simulations with lightning impulse and switching impulse