TIAN Qing. Analysis on the Measured Recovery Voltage in Artificial Single-Phase Grounding Test for UHV AC Pilot Project[J]. High voltageapparatus, 2010, 46(2): 1-4.
TIAN Qing. Analysis on the Measured Recovery Voltage in Artificial Single-Phase Grounding Test for UHV AC Pilot Project[J]. High voltageapparatus, 2010, 46(2): 1-4. DOI: 10.13296/j.1001-1609.hva.2010.02.003.
Analysis on the Measured Recovery Voltage in Artificial Single-Phase Grounding Test for UHV AC Pilot Project
The characteristic of recovery voltage of transmission line in artificial single phase grounding test for 1 000 kV UHV Pilot Project of State Grid Corporation of China is analyzed
and the corresponding single-phase reclosing scheme is discussed.It is found that the amplitude of recovery voltage can be restricted if the shunt compensators and neutral grounding reactor are set properly.The UHV transmission line with higher compensation level has lower beat frequency
which facilitates suppression of the secondary arc current.The single-phase reclosing scheme can be further improved when sufficient data is collected and subsequent research is done.