LI Zhen-qiang, ZHOU Pei-hong, XIU Mu-hong, et al. Research of AC Filter Bus Connecting Shunt-Reactor Resonance and Overvoltage[J]. High voltageapparatus, 2010, 46(2): 27-30+34.
LI Zhen-qiang, ZHOU Pei-hong, XIU Mu-hong, et al. Research of AC Filter Bus Connecting Shunt-Reactor Resonance and Overvoltage[J]. High voltageapparatus, 2010, 46(2): 27-30+34. DOI: 10.13296/j.1001-1609.hva.2010.02.010.
Research of AC Filter Bus Connecting Shunt-Reactor Resonance and Overvoltage
connecting system EMTP model of converter station has been built.Frequency scan is used to get the relation of system resonant frequency with bus voltage when AC filter bus shunt-reactor is connected in.Operating the bus shunt-reactor can cause overvoltage.Calculation results indicate that no resonant overvoltage generated during bus reactor closing and no overload generated during AC filters closing.However
with the increase of chopping current
this overvoltage generated by opening bus reactor(including breaker TRV and RRRV) is higher.It is effective to restrict the overvoltage that a group of arrestors are installed in parallel at the reactor side.