WANG Yu-lu1, WEI Bin2, HAO Xi-wei1, et al. Study on Neutral Point Grounding Method with Low Reactant for Main Transformers in Xi′an Power Grid[J]. High voltageapparatus, 2010, 46(2): 91-94.
WANG Yu-lu1, WEI Bin2, HAO Xi-wei1, et al. Study on Neutral Point Grounding Method with Low Reactant for Main Transformers in Xi′an Power Grid[J]. High voltageapparatus, 2010, 46(2): 91-94. DOI: 10.13296/j.1001-1609.hva.2010.02.023.
Study on Neutral Point Grounding Method with Low Reactant for Main Transformers in Xi′an Power Grid
摘要
针对目前西安电网中变压器中性点接地方式存在的安全隐患
提出了330 kV自耦变压器和110 kV变压器都经过小电抗接地的优化方式。仿真计算表明
经过适当的小电抗接地后
330 kV自耦变110 kV侧母线上的单相短路电流明显减小
其他110 kV变压器中性点过电压显著减小
保证了中性点绝缘不受威胁和系统运行的安全性。
Abstract
To get rid of the latent danger induced by the current neutral point grounding way of transformers in Xi’an power grid
an optimal grounding method of 330 kV auto-transformers and 110 kV transformers through a low reactance is proposed.The simulation results reveal that after grounding through low reactance with appropriate value
the single-phase grounding short-circuit current on the 110 kV bus-bar of 330 kV auto-transformer decreases clearly
and the over-voltage on neutral point of other 110 kV transformers is significantly reduced to a lower level
which guarantee safe insulation of neutral point and enhance reliability of the power grid.