DU Ning1, GUAN Yong-gang1, ZHANG Jing-sheng2, et al. Three-phase Modeling of Vacuum Circuit Breakers Switching off Shunt Reactors[J]. High voltageapparatus, 2010, 46(3): 6-9+14.
DU Ning1, GUAN Yong-gang1, ZHANG Jing-sheng2, et al. Three-phase Modeling of Vacuum Circuit Breakers Switching off Shunt Reactors[J]. High voltageapparatus, 2010, 46(3): 6-9+14. DOI: 10.13296/j.1001-1609.hva.2010.03.002.
Three-phase Modeling of Vacuum Circuit Breakers Switching off Shunt Reactors
Aiming at the operating conditions of 40.5 kV vacuum circuit breaker switching off shunt reactors
and in order to eliminate deficiencies in the existing simulation model
a general review of simulating researches on vacuum circuit breakers switching off small reactive current is given.A three-phase model of 40.5 kV circuit breakers switching off shunt reactors is set up based on the experimental results of a type of 4.5 kV vacuum circuit breaker
including the dielectric strength characteristics
high-frequency current quenching criteria and chopping current.And the interphase coupling is considered in the model.A three-phase simulation is conducted for the transient process of the vacuum circuit breaker switching off shunt reactors via ATP-EMTP
and the simulation results coincide almost with experimental results.