Study on the Lightning Protection Problem of 35 kV Transmission and Distribution Line
Lightning strike is one of the important reasons which cause the 35 kV distribution lines faults.Lightning activity is frequent in hilly areas
and will do great detriment to the safe operation of 35 kV overhead lines.There are two indexes to evaluate the line lightning protection performance: the one is the lightning trip-out rate
the other is the lightning withstand level of the power line.This paper analyzes the present situation of lightning protection of 35 kV line in Henan.It is considered that line has low insulation level
severe insulator aging
incomplete operation and maintenance
inadequate lightning protection measures
which lead the 35 kV distribution line has high lightning trip-out rate.The results show that: roundly detect the insulators
replace the poor-quality insulators
install the line surge arrester with series gap
improve the insulation level of line
meanwhile
use shunt gap as the lightning protection
erect lightning shield conductor
etc measures can significantly reduce lightning accidents.