WU Ming-xiang1, BAO Jian-qiang2, WANG Jian-ming3, et al. Analysis of a Breakdown Failure of Prefabricated 220 kV Cable Joint[J]. High voltageapparatus, 2010, 46(5): 95-97.
WU Ming-xiang1, BAO Jian-qiang2, WANG Jian-ming3, et al. Analysis of a Breakdown Failure of Prefabricated 220 kV Cable Joint[J]. High voltageapparatus, 2010, 46(5): 95-97. DOI: 10.13296/j.1001-1609.hva.2010.05.004.
Analysis of a Breakdown Failure of Prefabricated 220 kV Cable Joint
A breakdown failure of prefabricated cable joint occurred on the 220 kV cable line
and the spare joint with the same batch and specification cracked under normal pre-expansion during the process of urgent repair.The inspection
testing and cause analysis are conducted in this paper.According to the surface examination and discharge tracking analysis of the cracked EPDM rubber insulation on the broken-down joint
the main reason of this failure is the sudden crack of the insulation during operation process of the joint.Moreover
the cracked EPDM rubber insulation of the spare joint after normal expansion was checked by insulation aging test
and the result shows its breaking elongation ratio is low
which directly reduces the mechanical strength of the middle joint and leads to entire crack of the spare joint insulation.