Studies on the Overvoltage for Eliminating 750 kV Circuit Breaker Pre-inset Resistor
Eliminating pre-inset resistor of 750 kV circuit breaker can save costs and increase operation stability.A arresters were installed at both ends of 750 kV high voltage transmission line to suppress switching overvoltage.The effects of the number and positions of arrestor on the 750 kV Lanzhoudong-Yinchuandong transmission line on the switching over voltages
including three phases energizing line without load and single phase auto-reclosing
were analyzed using the electromagnetic transient program(ATP-EMTP).The results show that without any arresters
the maximum overvoltage while three phase energizing line with no load is 2.38 p.u.and for single auto-reclosing is 2.57 p.u.when the line is shorter and the install surge arresters at both ends
the ways can operate the above-mentioned two types of statistical overvoltage suppression to below 1.80
it can be seen when the abolition of the short circuit switch resistance is possible.