YANG Jing1, SHENG Hui-hui2, WEI Xiao-wei3. Analysis of a 500 kV Transformer Inner Short Circuit Damage[J]. High voltageapparatus, 2010, 46(6): 74-78. DOI: 10.13296/j.1001-1609.hva.2010.06.016.
Analysis of a 500 kV Transformer Inner Short Circuit Damage
An accident of 500 kV transformer inner short circuit is explored by the change analysis of the oil chromatogram after accident
the local discharge online monitoring
and ultimate degradation analysis.It is found that this accident is caused by inner short circuit of high voltage winding.The insulation effect analysis of the phenomenon of Cu2S in the accident is performed.The accident analysis also includes soldering quality