Altitude Correction Methods for Corona Loss of 750 kV Transmission Line
most of the 750 kV transmission lines in use or under construction are located in high altitude areas
leading to obvious corona loss. This paper takes the six-bundle conductor 6×LGJ-400/50 as an example to measure its corona loss by using the corona cage in an environmental climate laboratory with heavy rain condition
and the relation between corona loss and altitude within 0~4 000 m is achieved. Then reference standard and least-square method are employed to fit the measured data. Consequently
two different altitude correction formulas for corona loss are suggested.