RUAN Quan-rong, LI Hui, LIU Guo-feng, et al. Research on Arrangement of GIL Compartment in High Drop Vertical Shaft[J]. High voltageapparatus, 2010, 46(8): 52-55.
RUAN Quan-rong, LI Hui, LIU Guo-feng, et al. Research on Arrangement of GIL Compartment in High Drop Vertical Shaft[J]. High voltageapparatus, 2010, 46(8): 52-55. DOI: 10.13296/j.1001-1609.hva.2010.08.025.
Research on Arrangement of GIL Compartment in High Drop Vertical Shaft
The main considering factor of arrangement of GIL compartment in high drop vertical shaft is pressure difference which can be calculated by theory of static gas column.Through the engineering design studies and theoretical calculations
it shows that the height of pure SF6 gas compartment should not be more than 250 m
and the less pressure difference of SF6 mixture gas has less impact on the height of GIL compartment.It should provide two inflatable pressures for high drop vertical GIL shaft due to the influence of pressure difference.Considering that the temperature difference is the main influencing factor for pressure difference
it should pay attention to ventilation design of shaft.