Analysis and Treatment of Partial Discharge Excess in 4 500 A Thyristor Valve
The problem that the partial discharge level has exceeded acceptable level during dielectric type test of the KGWF-4500/167 thyristor valve that consists of 6 inch thyristor firstly was the dielectric problem
which could affect the safe and reliable operation of thyristor valve.By investigating with a UV camera detailed inspecting in this area
supposing the position appearing partial discharge and verifying it
writer conclude finally partial discharge activity appeared between the bracket and the lower water pipe.The reason partial discharge exceeded acceptable level was that the air clearance was not enough.After a minimum air clearance value has been assessed and verified
the laminate supporting plate has been redesigned by considering 30% margin of air clearance.So
the problem of partial discharge exceeded acceptable level has been resolved.The supporting plates have been redesigned and applied in actual xibei-huazhong BtB extending project.In this paper
a rapid method of finding
analyzing and solving problem witch comes forth during type test of actual project has been introduced.
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet
Related Author
YUE Song
GAO Fei
HAN Shuai
DONG Haoyuan
LI Jun
LI Xin
LIU Chao
QIAO Hui
Related Institution
Electric Power Research Institute of State Grid Tibet Company
China Electric Power Research Institute Co., Ltd.
Iflytek Co., Ltd.
Electric Power Research Institute, State Grid Hebei Electric Power Co., Ltd.
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University