LI Shun-yao, XIE Jian-rong. Test of Winding Deformation without Disconnection for 220 kV Transformer[J]. High voltageapparatus, 2010, 46(9): 88-91. DOI: 10.13296/j.1001-1609.hva.2010.09.022.
Test of Winding Deformation without Disconnection for 220 kV Transformer
摘要
变压器绕组变形测试是预防性试验不可缺少的试验项目
为提高工作效率
减少220 kV变压器拆接引线试验对设备造成的损害
大幅度降低试验拆接引线工作带来的高劳动强度
快速判断220 kV变压器绕组是否存在变形
笔者以频响法为主
短路阻抗法、电容变化法为辅
采用频响法、短路阻抗法、电容变化法3种方法
应用TDT5变形测试仪、HDZK-10 A低电压短路阻抗测试仪和AI600E型自动介损电桥
对220 kV变压器分别进行拆线与不拆线时绕组变形项目测试
通过3种试验方法所得数据进行对比分析
得出了220 kV变压器的变形测试项目可以用3种方法进行测试。
Abstract
To eliminate the harm of disconnecting winding leads to 220 kV transformer in winding deformation test
and rapidly judge whether winding deformation exists
the frequency response method
the short-circuit impedance method
and the electric capacity change method were adopted in 220 kV transformer winding deformation tests.A deformed winding was tested by TDT5 deformation tester
HDZK-10 A low voltage short-circuit impedance tester
and A1600E dielectric loss bridge
respectively
under two conditions of winding leads connection and winding leads disconnection.Comparison among the results from the three methods shows that all three methods can test winding deformation of 220 kV transformer without disconnecting the winding leads.