Damage Analysis of the DC Filter Capacitors in Tianshengqiao Converter Station with Countermeasures
DC filter capacitors often damage in recent years in Tianshengqiao con verter station.Some of the damaged capacitors were analyzed via disassembly in this study
consequently two countermeasures against the frequent damage were proposed.In the first measure
one or several original imported DC filter capacitors are replaced with the capacitors made in China;and in the second measure
the whole DC filter capacitors set is reformed.The first measure is superior to the second one in cost and applicability
and has been taken successfully in Tianshengqiao converter station.In China
DC filter capacitors in converter stations have long been depending on imported ones.Substituting single or some China-made DC filter capacitors for the imported ones in Tianshengqiao converter station is an attempt
and the dependence on these imported capacitors is abandoned.In addition
this study may benefit the application of the China-made DC filter capacitors in converter station of HVDC transmission projects.