Analysis of a Hydro-electric Station Grounding Device Problems and Rebuilding Measures
Aiming at the problems living in station grounding device
it is find that the problems were very complex which mainly contain bad connection
corrosion cracking
high grounding resistance
step voltage and contacting voltage exceeding through studying the grounding net structure of a hydropower station.According to soil resistivity testing on-site and combining with the regulation and actual condition
the measures were adopted which include expending grounding net partitioned
laying underwater grounding net
and balancing voltage for the reconstruction the grounding net.The calculation result shows that the grounding resistance dropping to 0.29 Ω from the former 1.199 Ω
after reconstruction
meeting the requirement 0.50 Ω.The conclusion is that the reconstruction example is typical
and it is of reference value to related electrical engineering problems.