The cooperation of AC-DC control and protection functions has important influence on the security and stability of the power system with the characteristics of long-distance
high power and combined operation of AC/DC.HVDC fundamental and second harmonic protections are the basic cooperation function between the AC and DC system.The 50 Hz and 100 Hz protection setting principles of the AC/DC hybrid transmission system are studied through EMTDC and RTDS simulation.The setting method based on the longest clearing time of AC faults and the overload capability of the HVDC main equipment is proposed
and the quantitative method based EMTDC simulation is presented.