DING Guo-cheng1, LI Wei1, WANG Liu-fang2, et al. Application of Ultraviolet Detection Technology for Corona Discharge to Abnormal on-line Infrared Detections[J]. High voltageapparatus, 2010, 46(10): 42-44.
DING Guo-cheng1, LI Wei1, WANG Liu-fang2, et al. Application of Ultraviolet Detection Technology for Corona Discharge to Abnormal on-line Infrared Detections[J]. High voltageapparatus, 2010, 46(10): 42-44. DOI: 10.13296/j.1001-1609.hva.2010.10.009.
Application of Ultraviolet Detection Technology for Corona Discharge to Abnormal on-line Infrared Detections
This paper introduced the treatment of an abnormity insulator and copper-tube bus of transformer detected by the infrared detector.And in order to know the cause of the faults
the authors used ultraviolet detector to monitor and analyze the abnormal on-line infrared detections based on the technology of ultraviolet detection.With the results detected by the ultraviolet detector
the abnormity of insulator was due to the small distance between the insulator and its grading ring
and the abnormity of copper-tube bus was due to the faradic current caused by the faradic electricity on the surface of copper-tube bus.So the position of grading ring was adjusted and the semi-insulated grading ring was replaced by insulated grading ring.Finally the ultraviolet detector was used to monitor the fault points again after treatment;the detections confirmed the right of the analyses and practicability of ultraviolet technology.