Research on Lightning Protection of 20 kV Overhead Insulated Lines
20 kV voltage level has been recognized that can replace the 10 kV voltage level in the world.Engineering applications showed that 20 kV transmission lines usually use overhead insulated cables
but its lightning stroke rate significantly higher than traditional bare overhead conductors.This paper makes a comprehensive analysis on lightning accident of the overhead insulated cables
calculates its amplitudes of the lightning overvoltage on the 20 kV overhead insulated distribution lines.The results show that the lightning over-voltage amplitude can be greater than 450 kV which over the existing insulation level of 20 kV lines.Drawing on the past lightning protection experiences and measures of the 10 kV transmission lines
this paper propose that comprehensively use zinc oxide arrester
overvoltage protection
shielding shunting line and other lightning protection measures to protect the 20 kV overhead insulated cables.This study provides a reference to the safe power supply of 20 kV distribution network.