YAN Yu-ting, JIANG Jian-wu, Wang Ya-zhou, et al. Theoretic of Testing Direct Current Resistance and Analysis of Different kind of Defects in Field[J]. High voltageapparatus, 2010, 46(10): 97-101.
YAN Yu-ting, JIANG Jian-wu, Wang Ya-zhou, et al. Theoretic of Testing Direct Current Resistance and Analysis of Different kind of Defects in Field[J]. High voltageapparatus, 2010, 46(10): 97-101. DOI: 10.13296/j.1001-1609.hva.2010.10.022.
Theoretic of Testing Direct Current Resistance and Analysis of Different kind of Defects in Field
Several kinds of transformer defects such as turn-to-turn short circuit
poor contact
can be judged by the result of the winding direct current(DC) resistance test.The theoretic and the methods to test DC Resistance
as well as the principle to deal with test results of exceeding rate have been explained in this paper.Then analysis based on different kinds of defects in field has been made.When turn-to-turn short circuit happened
the winding DC resistance would decrease;while poor contact happened between conductors
the winding DC resistance would increase.The importance and availability of testing deformation of transformers has been proved by a lot of experiments in substations.Combined with other electric test
the result can be much more effective in judging the situation of transformers.