LI Qing-ling1, XIA Hui-jun2, LI Hong-ren2, et al. Case Studies of Circuit Breaker[J]. High voltageapparatus, 2010, 46(11): 92-94. DOI: 10.13296/j.1001-1609.hva.2010.11.004.
Case Studies of Circuit Breaker
摘要
对某供电局220kV一变电站的真空断路器的故障情况进行了介绍。分析了两套保护装置的录波图
对受损坏的真空断路器进行了解体检查
校核了断路器的额定开断电流
详细分析了产生故障的原因
并从中得到了某些启示:投切电容器组的真空断路器必须进行电压和电流老炼试验
严格进行真空断路器的机械特性测试
注意高压开关柜的选型。提出了需要进一步加强的检查措施
为后续220kV开关设备提供了质量保证。
Abstract
This paper introduced the accident of a circuit breaker in 220 kV substation and analyzed the fault recording of two set of protective devices.Disassembly inspection of injured circuit breaker was performed;the breaking current of circuit breaker was checked;the causes of the accident were analyzed in detail.Some revelations are obtained:aging test of voltage and current and strict mechanical property test are necessary;paying attention to option of high voltage switch cabinet.Some measures for strict inspection of the 220 kV circuit breaker are suggested so as to enhance their safety.