Study of Restrike Overvoltage in the Test of Switching Small Capacity Current with Disconnector
In the test of switching small capacity current with a disconnector
the circuit might cause very fast transient overvoltage (VFTO) because of multiple restrikes of the disconnector
which makes the devices
especially the windings of transformer in the test circuit in great danger.VFTOs at the transformer terminals in switching processes were calculated by ATP-EMTP software
the factors that may affect the magnitude of restrike overvoltage were analyzed
and the protection effectiveness of adding gap at transformer output end against restrike overvoltage was analyzed.Simulation results show that restrike overvoltage is dependant on restrike time instead of arc time
and the resistance of arc channel imposes a prohibition on VFTO.Addition of protection gap at output end of a test transformer can clearly reduce its end overvoltage.