GU Chao-min, Sun Zhen-quan, Guo Zhi-feng, et al. Partial Discharge Characteristics of Internal Gas-gap Defect in Oil-paper Insulation System under AC and DC Composite Voltage[J]. High voltageapparatus, 2010, 46(12): 9-13.
GU Chao-min, Sun Zhen-quan, Guo Zhi-feng, et al. Partial Discharge Characteristics of Internal Gas-gap Defect in Oil-paper Insulation System under AC and DC Composite Voltage[J]. High voltageapparatus, 2010, 46(12): 9-13. DOI: 10.13296/j.1001-1609.hva.2010.12.004.
Partial Discharge Characteristics of Internal Gas-gap Defect in Oil-paper Insulation System under AC and DC Composite Voltage
For studying the partial discharge characteristics of oil-paper insulation in converter transformer at DC transmission system
a typical oil-paper partial discharge model-internal defect was made and a testing circuit which DC voltage superposed on AC voltage was designed and built to simulate the voltage component that the converter transformer withstand. Applied different proportion of DC and AC component in the composite voltage and detected the characteristic parameters of the test model with pulse current method to compare and study.Summarized the PD pulse rules of oil-paper insulation gas-gap discharge model under DC AC composite voltage and analyzed its discharge mechanism.The result showed that the PD characteristic of oil-paper insulation gas-gap model under composite voltage is different from that under AC and DC voltage only.Accumulated experience for on-line monitoring and comprehensive evaluation of converter transformer insulation.