ZHU Ge-lan1, WEI Chun-zhi2, WANG Gang1. Failure Analysis and Protection of High Voltage Capacitor in Three Tuned DC Filter[J]. High voltageapparatus, 2010, 46(12): 78-81.
ZHU Ge-lan1, WEI Chun-zhi2, WANG Gang1. Failure Analysis and Protection of High Voltage Capacitor in Three Tuned DC Filter[J]. High voltageapparatus, 2010, 46(12): 78-81. DOI: 10.13296/j.1001-1609.hva.2010.12.019.
Failure Analysis and Protection of High Voltage Capacitor in Three Tuned DC Filter
In Yun nan-Guang dong UHVDC transmission project there is only one capacitor with the high potential in the three tuned filter
which undertakes almost all DC high voltage and most of the harmonic voltage drop
easily leading to occurrence of failure because of voltage breakdown.The internal structure and operating condition of the capacitor are discussed first.The unbalanced current value and characteristics under the units fault
are deduced.which produced by the two bridge arms.Based on PSCAD / EMTDC the units model is established the simulation demonstrates that the unbalanced current has the fixed proportion relations with the sum of two branches current.Finally
the units protection modes which should depose to HV capacitor are put forward.