DUAN Xiong-ying, HUANG Zhi-hui, LI Rui, et al. Comparison between Two Methods of Zero-cross Point Prediction for Controlled Fault Current Interruption[J]. High voltageapparatus, 2011, 47(1): 5-9.
DUAN Xiong-ying, HUANG Zhi-hui, LI Rui, et al. Comparison between Two Methods of Zero-cross Point Prediction for Controlled Fault Current Interruption[J]. High voltageapparatus, 2011, 47(1): 5-9. DOI: 10.13296/j.1001-1609.hva.2011.01.005.
Comparison between Two Methods of Zero-cross Point Prediction for Controlled Fault Current Interruption
rapid prediction of zero-cross point of objective current is a key factor
however a difficult problem.Two major rapid algorithms for predicting the zero-cross point
i.e.the safe-point algorithm and the adaptive self-checking algorithm
were hence proposed.This paper discussed the two algorithms via theoretical analysis and simulation.A single-phase short circuit fault current model was established to analyze and compare the suitability of two algorithms.The results show that for the short circuit fault current model without harmonics
the adaptive self-checking algorithm can predict the zero-cross point of objective current with higher precision
and for the short circuit fault current model with harmonics
the safe-point algorithm works easier and can achieve better waveform.However
both algorithms can only be applied to the system with single-phase fault.