MU Xiu-qing1, FANG Chun-en1, Dong En-yuan2, et al. Fault Type Identification for Controlled Interruption of Synchronous Circuit Breaker Based on Correlation Analysis[J]. High voltageapparatus, 2011, 47(1): 39-42+48.
MU Xiu-qing1, FANG Chun-en1, Dong En-yuan2, et al. Fault Type Identification for Controlled Interruption of Synchronous Circuit Breaker Based on Correlation Analysis[J]. High voltageapparatus, 2011, 47(1): 39-42+48. DOI: 10.13296/j.1001-1609.hva.2011.01.011.
Fault Type Identification for Controlled Interruption of Synchronous Circuit Breaker Based on Correlation Analysis
Controlled interruption of fault currents can increase the interrupting capacity of high voltage synchronous circuit breakers and prolong the electrical life of circuit breaker contacts.One of the most important factors for controlled interruption of multi-phase fault currents is the detection of fault phase and type.In this paper
the phase position relationship of positive sequence and negative sequence fault components was obtained via correlation analysis to determine the fault phase rapidly and precisely.Furthermore
an interrupting fault current model of high voltage circuit breaker based on MABLAB was constructed to verify the proposed method.The results show that the proposed method can detect the fault phases within the latter half cycle after fault initiation
and may provide theoretical basis and implementation for controlled interruption of fault current.