LI Xiao-feng1, HUO Feng-ming1, ZHEN Li2. Operational Status Evaluation of Circuit Breaker by Detecting SF6 Decomposition Products[J]. High voltageapparatus, 2011, 47(1): 103-105.
LI Xiao-feng1, HUO Feng-ming1, ZHEN Li2. Operational Status Evaluation of Circuit Breaker by Detecting SF6 Decomposition Products[J]. High voltageapparatus, 2011, 47(1): 103-105. DOI: 10.13296/j.1001-1609.hva.2011.01.021.
Operational Status Evaluation of Circuit Breaker by Detecting SF6 Decomposition Products
摘要
个别SF6柱式断路器在运行中曾发出断续的声响
解体后发现声响原因为绝缘拉杆金属接头的轴销与轴孔产生悬浮电位
产生间歇放电并发出声响
导致轴销和轴孔腐蚀严重
甚至被腐蚀断裂。针对该类缺陷
曾利用特高频、声波、人工耳听等方法对在运设备进行诊断
但收效甚微
人工耳听还容易误判或漏判。笔者通过对一起SF6断路器拉杆轴销断裂故障原因及后续治理方法的分析
提出通过对SF6气体分解物进行检测分析来判断断路器运行状态的方法
早期发现断路器内部轴销及轴孔腐蚀隐患
同时通过实际案例验证了该方法的有效性和实际意义。
Abstract
Discontinuous sound had been heard in some SF6 pillar circuit breakers during operation.By disassembling these breakers
this sound was found to be caused by the intermittent discharge due to the suspension potential between the axle pin and hole of the metal joint on an insulated draw rod.Th edischarge eroded or even broke the axle pin and hole.UHF
ultrasonic and hearing detection methods have been used to diagnose this fault
however the results were not satisfactory
and the hearing method might bring about misjudgement.Through the analysis of an axle pin fracture fault of draw rod on an SF6 pillar circuit breaker and the treatment method
this study presented a method for evaluating operational status of the breakers by detecting the SF6 decomposition products in order to detect and eliminate early internal-discharge in the breakers.This method was validated by a real case.