LIN Xin, CAI Qiang, XU Jian-yuan, et al. Large Scale of Electric Field Calculation of 1 100 kV Disconnector Based on Domain Decomposition Method[J]. High voltageapparatus, 2011, 47(2): 1-6.
LIN Xin, CAI Qiang, XU Jian-yuan, et al. Large Scale of Electric Field Calculation of 1 100 kV Disconnector Based on Domain Decomposition Method[J]. High voltageapparatus, 2011, 47(2): 1-6. DOI: 10.13296/j.1001-1609.hva.2011.02.001.
Large Scale of Electric Field Calculation of 1 100 kV Disconnector Based on Domain Decomposition Method
and low efficient solution have been confronted when solving large engineering electromagnetic problems by finite element method
therefore
the domain decomposition method was taken into account to solve this problem.The 3D electric field model of UHV disconnector(DS) was set up after expounding the principle the domain decomposition method
the results calculated by which were compared with those of calculation by integrated method
which demonstrated that the storage space constrain was mitigated and the efficiency was enhanced by domain decomposition method.Then the capacitance parameters of DS chamber were calculated by means of electric field energy programmed by APDL.The calculated values were compared with measured ones