LI Yi1, ZHOU Ye1, ZHONG Hao1, et al. Recognition of Flashover Fault on the Iced Insulator Based on Frame Segmentation and Wavelet Technology for Leakage Current[J]. High voltageapparatus, 2011, 47(2): 27-30.
LI Yi1, ZHOU Ye1, ZHONG Hao1, et al. Recognition of Flashover Fault on the Iced Insulator Based on Frame Segmentation and Wavelet Technology for Leakage Current[J]. High voltageapparatus, 2011, 47(2): 27-30. DOI: 10.13296/j.1001-1609.hva.2011.02.006.
Recognition of Flashover Fault on the Iced Insulator Based on Frame Segmentation and Wavelet Technology for Leakage Current
The traditional leakage current’s time-frequency analysis method has some insufficiencies.Through dynamic measuring leakage current on the 3-piece string iced insulators at ice-melting stage in artificial climate chamber
this paper proposed that uses frame segmentation method to calculate the reference values:the extreme value of short-time energy signal and zero-cross signal.Through using wavelet decomposition reconstructing the envelope curves of energy signal and zero-cross signal
provides early warning for iced insulators flashover fault from both data and curve aspects.