Analysis and Treatment of a Closing Fault of a 252 kV SF6 Circuit Breaker
this paper analyzed the causes of closing fault in a 252 kV SF6 circuit breaker in Chongqing Power Grid.The chemical reaction of SF6 with water and grease under high temperature arc and it’s substances leakage into the sealed components caused the jam.Maintenance about the body of the circuit breaker proved that situation.Finally
some suggestions and methods were proposed to take care during the maintenance for the fault
which can be referred to the similar faults and make the normal operation of the power grid.