JIANG Zhen. Analysis on Insulation Structure of Barrier System of Converter Transformer[J]. High voltageapparatus, 2011, 47(3): 69-71+76. DOI: 10.13296/j.1001-1609.hva.2011.03.013.
Analysis on Insulation Structure of Barrier System of Converter Transformer
Reliability of DC barrier system is one of key points of converter transformer’s R&D.DC barrier systems are imported over the years.Optimization of insulation structure of barrier system has significant influence on further speeding up localization manufacture of converter transformer in China.The operation characteristic of converter transformer was summarized
and the insulation structure of barrier system was studied.Furthermore
the calculation of electric field of insulation structure for DC barrier system was made.Converter transformer has features as high short circuit impedance
DC bias current influence
serious influence of harmonic and complicated insulation structure.Electric field analysis and calculation was carried on the basis of typical insulation structure of DC barrier system for different models under different testing condition
such as long duration AC applied voltage withstand test
DC voltage withstand test with PD measurement and polarity reversal test to summarize design concept and main points to structure of DC barrier system.Test results show that the developed insulation structure of DC barrier system is reasonable
which has been approved by the test.The same theory and method will be applied to insulation structure electric field analysis of DC barrier system of converter transformer with higher voltage level to optimize the sound insulation structure of DC barrier system.