Analysis of Potential Transformer Burning-out and Fuse’s Blowing in Local Power System
due to the nonlinear characteristic of excitation inductance of three-phase electromagnetic potential transformer
the ferroresonance overvoltage is easy to occur under a certain condition
leading to breakdown of the inner insulation
discharge of the external insulation
and blowing of the fuse.This accident often results in outage in large area because of delay in dealing with.This paper analyzed two ferroresonance overvoltage accidents caused by 10 kV single-phase grounding and 35 kV single-phase grounding
which induced the capacitor at 10 kV side to transfer overvoltage.The causes of the accidents were found
and the prevention measures were suggested correspondingly.Examples support the measures.