ZHONG Tian-xiang, JIN Shu-jun. Analysis on Misoperation Reasons of 500 kV Transformers Gas Relay[J]. High voltageapparatus, 2011, 47(5): 79-82. DOI: 10.13296/j.1001-1609.hva.2011.05.015.
Analysis on Misoperation Reasons of 500 kV Transformers Gas Relay
Gas relay is the main protection of the main transformer
and this protection is the key of the transformer’s safety.This article introduced the operation process of the heavy gas protection of the 500 kV transformer
described the configuration and the operative elements of the gas relay
finally presented the reasons: the closing excitation inrush current is large
some gas in the transformer
behavioral value of the gas relay is low
at the same time
put forward the corresponding proposal about transformer’s use