HUANG Tao1, WEN Yuan-fang1, WEN Kang-zhen2, et al. Study on Voltage Distribution along Insulator Strings of EHV/UHV AC Transmission Line Based on Circuit Equivalent Transformation[J]. High voltageapparatus, 2011, 47(7): 29-34.
HUANG Tao1, WEN Yuan-fang1, WEN Kang-zhen2, et al. Study on Voltage Distribution along Insulator Strings of EHV/UHV AC Transmission Line Based on Circuit Equivalent Transformation[J]. High voltageapparatus, 2011, 47(7): 29-34. DOI: 10.13296/j.1001-1609.hva.2011.07.005.
Study on Voltage Distribution along Insulator Strings of EHV/UHV AC Transmission Line Based on Circuit Equivalent Transformation
A new method based on circuit equivalent transformation for calculation of insulator strings is proposed in the paper.This method can be used in every condition which is comparable with the electric-network method.What’ more
it is much more efficient than other methods
and is easy to be developed into programs by a variety of programming languages.By artificial pollution test
range of the self capacitance and self resistance of the insulator in various conditions(perfect
faulty
clean
polluted) is determined as the input of the simulation program.The simulation result of the voltage distribution along insulator strings of a 500 kV EHV AC transmission line is in line with the actual.Simulation to the voltage distribution along insulator strings of a 1 000 kV UHV AC transmission line shows that corona rings should be installed for a better voltage distribution.The stray capacitance between corona ring and insulators should be about 13 pF to obtain best distribution
which appeared when corona rings were installed at 3-unit-long cover depth.