Measurement and Analysis of the Zero Sequence Impedance of the Double Circuit Transmission Line
When the zero-sequence impedance of circuit Ⅰ of the double circuit transmission line is measured
zero-sequence induced current will flow through the path composed of overhead ground wire
earth and another circuit Ⅱ which is short connected and grounded in two ends and can be considered as shielding line with two terminals grounded
due to the mutual inductance between them.The path of those grounded lines is equivalent to a shorted secondary coil of circuit Ⅰ and cause demagnetization on its magnetic field.The measured value of zero-sequence impedance amplitude will be reduced as a result of the path formed by those grounded lines and the zero-sequence impedance angle will also be affected.Inaccuracy can be caused by this measurement error of zero-sequence impedance to relay protective setting
power flow calculation and stability analysis.This article analyzes Double Circuit Transmission Line with continuous ground zero sequence impedance grounding of the accuracy of measurement results
By EMTP of typical double-circuit transmission line tower with zero sequence impedance simulation
And analysis of the four 500 kV lines
two 220 kV lines
zero sequence impedance of the measured results
the measurement issues that should be noted
it puts forward some problems that should be paid attention to during the process of measurement and calculation.