Simulation Research of Transient Over-voltage on High-voltage Shunt Capacitor Banks
摘要
With the development of power systems
a large number of shunt capacitors are used to improve power quality in the distribution network.The shunt capacitor banks are operated much frequently
as a result
the capacitor banks will bear large numbers of over-voltage inevitably.If the over-voltage exceeds certain amplitude
the capacitor will be damaged.This paper aims at the capacitor banks in the 35 kV side of Shanghai Xu-xing 500 kV substation
and applies ATP-EMTP to simulate the over-voltages generated by operating the switches under different angles of the source.Finally
according to the results of simulation and theoretical analysis
a best choice(i.e.angles of the source) to switch on capacitor banks is proposed.In this case the over-voltage on the capacitor will be limited to lowest.
Abstract
With the development of power systems
a large number of shunt capacitors are used to improve power quality in the distribution network.The shunt capacitor banks are operated much frequently
as a result
the capacitor banks will bear large numbers of over-voltage inevitably.If the over-voltage exceeds certain amplitude
the capacitor will be damaged.This paper aims at the capacitor banks in the 35 kV side of Shanghai Xu-xing 500 kV substation
and applies ATP-EMTP to simulate the over-voltages generated by operating the switches under different angles of the source.Finally
according to the results of simulation and theoretical analysis
a best choice(i.e.angles of the source) to switch on capacitor banks is proposed.In this case the over-voltage on the capacitor will be limited to lowest.