LU Ming1, YANG Qing2, YAN Dong1. Study and Application of the Series Connection of Glass Insulator to Improve the Electric Field Distribution on Composite Insulator[J]. High voltageapparatus, 2011, 47(10): 12-18+25.
LU Ming1, YANG Qing2, YAN Dong1. Study and Application of the Series Connection of Glass Insulator to Improve the Electric Field Distribution on Composite Insulator[J]. High voltageapparatus, 2011, 47(10): 12-18+25. DOI: 10.13296/j.1001-1609.hva.2011.10.004.
Study and Application of the Series Connection of Glass Insulator to Improve the Electric Field Distribution on Composite Insulator
The strong electric field near the end of composite insulator metal fitting is caused by the asymmetrical electric field distribution for the configuration characteristic
which becomes higher and higher with the increase of the voltage level and the length of insulator.The insulator life-span is reduced by partial discharge on the insulation material and the surface of the metal electrodes which is harmful to the safe operation of the power system.The results show that by this means
the voltage applied on the composite side of composite insulators is lowered;distorted electric field is eliminated;the electric field distribution in the ends of composite insulators is improved.Finally
this thesis recommends the number of glass insulators which should be installed in the high voltage side of composite insulators at different levels.