MAO Chen-lin, ZHANG Si-jiang, TAN Yan-min. Dielectric Loss Test and Analysis of 750 kV CVT Intermediate Transformer[J]. High voltageapparatus, 2011, 47(10): 60-62+68.
MAO Chen-lin, ZHANG Si-jiang, TAN Yan-min. Dielectric Loss Test and Analysis of 750 kV CVT Intermediate Transformer[J]. High voltageapparatus, 2011, 47(10): 60-62+68. DOI: 10.13296/j.1001-1609.hva.2011.10.012.
Dielectric Loss Test and Analysis of 750 kV CVT Intermediate Transformer
摘要
介绍了750 kV CVT中间变压器现场介损试验的现场测试情况
分析了试验数据超标的原因及按照规程中规定的介损标准进行设备绝缘状态判定的难度
并提出了下一步如何在现场进行交接试验判断CVT电磁单元绝缘状况的建议。
Abstract
Field dielectric loss test of 750 kV CVT intermediate transformer is introduced;the reason why the test data exceed criterion is analyzed;the difficulty in evaluation of equipment insulation status in accordance with the dielectric loss values from the related regulations and standards is discussed
and an suggestion for insulation judgment of CVT electromagnetic unit through field handover test is offered.
Dielectric Loss Digital Algorithm Combined with Median Filter
The Lectotype of CVT in UHV AC Pilot Demonstration Project
Influence of Grading Ring’s Paint Film on Measurement of Grading Capacitor’s Dielectric Loss
Correlation Study of Water Tree and VLF tanδ Based on Pearson Correlation Coefficient
Statistical Analysis of Dielectric Loss of Transformer Bushing Based on Significance Difference
Related Author
LI He-ming
LU Fang-cheng
XU Zhi-niu
YE Guo-xiong
WANG Xiao-qi
WU Shi-pu
LU Jian-ren
SUN Heng-feng
Related Institution
华北电力大学电力系统保护与动态安全监控教育部重点实验室 河北保定071003
Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control under Ministry of Education, North China Electric Power University