FENG Dong1, LUO Hai-zhi3, YANG Jie-min4, et al. Principle and Improvement of the Earth Electrode Overvoltage Protection for an HVDC Project[J]. High voltageapparatus, 2011, 47(12): 49-55.
FENG Dong1, LUO Hai-zhi3, YANG Jie-min4, et al. Principle and Improvement of the Earth Electrode Overvoltage Protection for an HVDC Project[J]. High voltageapparatus, 2011, 47(12): 49-55. DOI: 10.13296/j.1001-1609.hva.2011.12.010.
Principle and Improvement of the Earth Electrode Overvoltage Protection for an HVDC Project
The principle of the earth electrode overvoltage protection of the Gui-GuangⅡ HVDC Project is analyzed
and the protection logic of the earth electrode overvoltage protection(59EL) is described.Through analyzing the behaviour of 59EL in the commissioning process of the Gui-GuangⅡ HVDC Project
the bugs in the 59EL are found.In order to eliminate the bugs in protection logic
avoid the monopolar block or even bipolar blocks due to misoperation of 59EL
and improve the reliability of HVDC operations
some improvement solutions are offered for modifying 59EL logic in the Gui-GuangⅡ HVDC Project
and improving the programs of pole control system and DC station control system.In addition
RTDS simulations are conducted to verify the proposed improvement solutions.