LI Yong-ming1, CHEN Xiao-xin1, ZHANG Huai-qing1, et al. Calculation of Ion Current Field under HVDC Transmission Line Considering Ground Potential Rise[J]. High voltageapparatus, 2012, 48(1): 17-24.
LI Yong-ming1, CHEN Xiao-xin1, ZHANG Huai-qing1, et al. Calculation of Ion Current Field under HVDC Transmission Line Considering Ground Potential Rise[J]. High voltageapparatus, 2012, 48(1): 17-24. DOI: 10.13296/j.1001-1609.hva.2012.01.007.
Calculation of Ion Current Field under HVDC Transmission Line Considering Ground Potential Rise
a model for calculating ion current field under high-voltage direct-current(HVDC) transmission line is established with the charge simulation method by taking ground potential rise(GPR) as the first boundary condition.The calculation results without considering GPR agree well with those from Teshmont Corporation
and the calculation results considering GPR show that the maximum electric field strength and ion current density on the ground in rainy weather increase by around 200% and 150%
respectively.Moreover
the impact of ground potential variation on the resultant electric field under HVDC transmission line is analyzed for different magnitudes of GPR