GU Le1, CHEN Jun2, LIU Wen-hao2, et al. Impact Factors of Disc Sensor for Partial Discharge in GIS[J]. High voltageapparatus, 2012, 48(2): 55-59. DOI: 10.13296/j.1001-1609.hva.2012.02.003.
Impact Factors of Disc Sensor for Partial Discharge in GIS
Partial discharge(PD) detection is an important insulation diagnosis method in gas insulated switchgear(GIS) to prevent accidents.UHF disc sensor has high sensitivity and low noise level to monitor PD of GIS.The paper investigates the characteristic of the sensor which is related to the structure of the sensor and the GIS tank by simulation.The results show that the input impedance and voltage standing wave ratio(VSWR) of the sensor will decrease with the increase of the dielectric constant
the sensor’s diameter
the line’s diameter and the the distance between the disc and the ground plate.It can be helpful to the match between the sensor and output cable.In addition
the sensor’s gain doesn’t change significantly with the structure of itself in high frequency
but it will become higher when the GIS tank exists.