FAN Rong-quan1, CAO Mei-gen2, ZHUO Yue3, et al. Analysis on Aseismic Capacity of High Voltage Breaker and Aseismic Measures[J]. High voltageapparatus, 2012, 48(3): 12-16+20.
FAN Rong-quan1, CAO Mei-gen2, ZHUO Yue3, et al. Analysis on Aseismic Capacity of High Voltage Breaker and Aseismic Measures[J]. High voltageapparatus, 2012, 48(3): 12-16+20. DOI: 10.13296/j.1001-1609.hva.2012.03.004.
Analysis on Aseismic Capacity of High Voltage Breaker and Aseismic Measures
High voltage circuit breakers are one of the key electrical equipment in power systems which aseismic capacity is weak.Firstly
survey and analysis on earthquake disaster of circuit breakers in 5.12 Wenchuan earthquake are carried on.In addition
acceleration and stress response of SF6 circuit breaker
subjected by varied earthquake wave in shaking table testing.As is shown that damage of circuit breakers is severe in the above Ⅶ level(earthquake intensity) region.Generally
there are four types of typical damage.It is essential that some effective aseismic measures are adopted to improving aseismic capacity for circuit breakers.There are two methods to enhance circuit breaker aseismic capacity
one is conventional aseismic technology
another is isolation and damping technology which have obvious advantages for the distinct principle and notable efficiency.Finally
considering to structural feature
the three suitable schemes on isolation and damping technology of circuit breaker are put forward.This research has some certain reference to aseismic design and reinforcement of circuit breaker electrical equipment.